Fire Safety Inspections
Fire Safety Inspections
The City of Battle Ground inspects businesses, schools and facilities under the authority of the International Fire Code. The Fire Code edition is adopted & amended by the State of Washington and by the Battle Ground City Council by ordinance under title 15 of the Battle Ground Municipal Code.

In additional to our regular inspection intervals, staff also respond to complaints alleging violations of the fire & life safety provisions of the Fire Code.

Pre-Inspection Checklist
The following are some of the most common fire code violations found during inspections. Please be sure to walk through your facility and correct any conditions that meet these requirements.

Housekeeping
• Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms. (IFC 315.2.3)

• Combustible materials shall not be stored in exits or exit enclosures. (IFC 315.2.2)

• Outside dumpster shall be kept at least 5 feet away from combustible walls, windows, doors, overhangs and lid shall be closed. (IFC 304.3.3)

• Combustible storage shall be at least 2 feet below the ceiling or 18 inches below sprinkler heads. (IFC 315.2.1)

• Compressed gas containers, cylinders and tanks shall be secured to prevent falling. (IFC 3003.5.3)

Exits
• Exit ways and doors shall not be visually or physically obstructed. (IFC 1030.3 & .6)

• Exit ways and doors shall be unlocked when building is occupied. (IFC 1008.1.9)

• Exit signs shall be illuminated. (IFC 1011.2)

• Emergency lighting systems shall be functional. (IFC 1006.3)

• Fire assemblies shall not be obstructed or otherwise impaired from their proper operation at any time. (IFC 703.2)

• Main door shall have a sign above door stating “THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED.” unless approved panic hardware is in place (IFC 1008.1.9.3)

Fire Protection
• All fire lanes, hydrants, fire department connections (F.D.C.) or control valves shall be clear and unobstructed. (IFC 503.4 & 507.5.4)

• Sprinkler or fire alarm systems shall be serviced annually. (IFC 903.5 & 907.9.2)

• Fire protection systems shall be maintained in an operative condition at all times and repaired where defective. (IFC 907.9.1)

Commercial Cooking Processes
• A Class K fire extinguisher shall be mounted within 30 feet of commercial food equipment using vegetable or animal oils (IFC 904.11.5)

• Commercial cooking systems shall be serviced semi-annually. (IFC 904.11.6.2)

• Hoods, grease removal devices, fans, ducts and other appurtenances shall be cleaned to bare metal. Cleaning shall be recorded, and records shall state the extent, time and date of cleaning. Records shall be maintained on premises. (IFC 609.3.3)

Building Maintenance
• The building address shall be clearly visible from the street, minimum 4 inches in height with a contrasting background. (IFC 505.1)

• Provide Knox box for buildings with supervised fire protection equipment (IFC 506.1)

• Provide keys for Knox box (IFC 506.2)

• Fire-resistance-rated construction shall be maintained. (IFC 703.1)

• Provide legible & permanent sign with occupant load posted in conspicuous location. (IFC 1004.3)

Electrical
• A working space of not less than 30 inches wide (or width of equipment), 36 inches deep and 78 inches high shall be provided in front of electrical service equipment. No storage within this designated work space. (IFC 605.3)

• Relocatable power taps shall be polarized or grounded equipped with over-current protection and shall be listed. (IFC 605.4.1)

• Relocatable power taps shall be directly connected to a permanently installed receptacle. (IFC 605.4.2)

• Relocatable power tap cords and extension cords shall not extend through walls, ceilings, floors, under doors or floor coverings, or be subject to environmental or physical damage. (IFC 605.4.3)

• Extension cords and flexible cords shall not be a substitute for permanent wiring. (IFC 605.5)

Portable Fire Extinguishers
• A minimum of one 2A-10:BC portable fire extinguisher shall be provided within 75 feet of travel distance from anywhere in the business on each floor. (IFC 906.3 – NFPA 10)

• Fire extinguishers shall not be obstructed and shall be in a conspicuous location. (IFC 906.5)

• When visually obstructed, an approved means shall be provided to indicate location. (IFC 906.6)

• Fire extinguisher shall be mounted on wall with hanger. (IFC 906.7)

• Fire extinguishers shall be serviced and tagged annually by a certified individual 906.2


Contact

Erin Erdman
Community Development Director
Contact Me

Mark Miller
Building Official
Contact Me

109 S.W. 1st St., Suite 123
Battle Ground, WA 98604

Ph: (360) 342-5046
Fx: (360) 342-5049

Inspection Line
Ph: (360) 342-5085

Staff Directory

Counter Hours
Mon-Wed-Fri
8:00 am - 5:00 pm
Tue - Thu
8:00 am - 1:00 pm